home *** CD-ROM | disk | FTP | other *** search
- Frequently Asked Questions (FAQS);faqs.032
-
-
-
- The two pairs of connections on a GFCI outlet are not symmetric.
- One is labeled LOAD; the other, LINE. The incoming power feed
- *must* be connected to the LINE side, or the outlet will not be
- protected. The LOAD side can be used to protect all devices
- downstream from it. Thus, a whole string of outlets can be
- covered by a single GFCI outlet.
-
- Subject: Where should GFCIs be used?
-
- The NEC mandates GFCIs for 110V, 15A or 20A single phase
- outlets, in bathrooms, kitchens within 6' of the sink, garages,
- unfinished basements or crawl spaces, outdoors, near a pool, or
- just about anywhere else where you're likely to encounter water
- or dampness. There are exceptions for inaccessible outlets,
- those dedicated to appliances ``occupying fixed space'',
- typically refrigerators and freezers, and for sump pumps and
- laundry appliances.
-
- The CEC does not mandate as many GFCIs. In particular, there
- is no requirement to protect kitchen outlets, or most garage or
- basement outlets. Basement outlets must be protected if you
- have a dirt floor, garage outlets if they're near the door to
- outside. Bathrooms and most exterior outlets must have GFCIs.
-
- Even if you are not required to have GFCI protection, you may
- want to consider installing it anyway. Unless you need a GFCI
- breaker (see below), the cost is low. In the U.S., GFCI
- outlets can cost as little as US$8. (Costs are a bit higher in
- Canada: C$12.) Evaluate your own risk factors. Does your
- finished basement ever get wet? Do you have small children?
- Do you use your garage outlets to power outdoor tools? Does
- water or melted snow ever puddle inside your garage?
-
- Subject: Where shouldn't I use a GFCI?
-
- GFCIs are generally not used on circuits that (a) don't pose a
- safety risk, and (b) are used to power equipment that must run
- unattended for long periods of time. Refrigerators, freezers,
- and sump pumps are good examples. The rationale is that GFCIs
- are sometimes prone to nuisance trips. Some people claim that
- the inductive delay in motor windings can cause a momentary
- current imbalance, tripping the GFCI. Note, though, that most
- GFCI trips are real; if you're getting a lot of trips for no
- apparent reason, you'd be well-advised to check your wiring
- before deciding that the GFCI is broken or useless.
-
- Subject: What is the difference between a GFCI outlet and a GFCI breaker?
-
- For most situations, you can use either a GFCI outlet as the
- first device on the circuit, or you can install a breaker with
- a built-in GFCI. The former is generally preferred, since GFCI
- breakers are quite expensive. For example, an ordinary GE
- breaker costs ~US$5; the GFCI model costs ~US$35. There is one
- major exception: if you need to protect a ``multi-wire branch
- circuit'' (two or more circuits sharing a common neutral wire),
- such as a Canadian-style kitchen circuit, you'll need a
- multi-pole GFCI breaker. Unfortunately, these are expensive;
- the cost can range into the hundreds of dollars, depending on
- what brand of panel box you have. But if you must protect such
- a circuit (say, for a pool heater), you have no choice.
-
- One more caveat -- GFCI outlets are bulky. You may want to use
- an oversize box when installing them. On second thought, use
- large (actually deep) boxes everywhere. You'll thank yourself for it.
-
- Incidentally, if you're installing a GFCI to ensure that one
- specific outlet is protected (such as a bathroom), you don't
- really have to go to all of the trouble to find the first
- outlet in the circuit, you could simply find the first outlet
- in the bathroom, and not GFCI anything upstream of it. But
- protecting the whole circuit is preferred.
-
- When you install a GFCI, it's a good idea to use the little
- "ground fault protected" stickers that come with it and mark
- the outlets downstream of the GFCI. You can figure out which
- outlets are "downstream", simply by tripping the GFCI with the
- test button and see which outlets are dead.
-
- Subject: What's the purpose of the ground prong on an outlet, then?
-
- Apart from their use in electronics, which we won't comment on,
- and for certain fluorescent lights (they won't turn on without
- a good ground connection), they're intended to guard against
- insulation failures within the device. Generally, the case of
- the appliance is connected to the ground lead. If there's an
- insulation failure that shorts the hot lead to the case, the
- ground lead conducts the electricity away safely (and possibly
- trips the circuit breaker in the process). If the case is not
- grounded and such a short occurs, the case is live -- and if
- you touch it while you're grounded, you'll get zapped. Of
- course, if the circuit is GFCI-protected, it will be a very
- tiny zap -- which is why you can use GFCIs to replace
- ungrounded outlets (both NEC and CEC).
-
- There are some appliances that should *never* be grounded. In
- particular, that applies to toasters and anything else with
- exposed conductors. Consider: if you touch the heating
- electrode in a toaster, and you're not grounded, nothing will
- happen. If you're slightly grounded, you'll get a small shock;
- the resistance will be too high. But if the case were
- grounded, and you were holding it, you'd be the perfect path to
- ground...
-
- Subject: Why is one prong wider than the other? Polarization
-
- Nowadays, many two-prong devices have one prong wider than the
- other. This is so that the device could rely (not guaranteed!)
- on one specific wire being neutral, and the other hot.
- This is particularly advantageous in light fixtures, where the
- the shell should neutral (safety), or other devices which want to
- have an approximate ground reference (ie: some radios).
-
- Most 2-prong extension cords have wide prongs too.
-
- This requires that you wire your outlets and plugs the right
- way around. You want the wide prong to be neutral, and the
- narrow one hot. Most outlets have a darker metal for the
- hot screw, and lighter coloured screw for the neutral.
- If not, you can usually figure out which is which by which
- prong the terminating screw connects to.
-
- Subject: What kind of outlets do I need in a kitchen?
-
- The NEC requires at least two 20 amp ``small appliance
- circuits'' for kitchens. The CEC requires split-duplex
- receptacles. Outlets must be installed such that no point is more
- than 24" (NEC) (900 mm CEC) from an outlet. Every counter wider
- than 12" (NEC) or 300 mm (CEC) must have at least one outlet.
- The circuit these outlets are on may not feed any outlets except
- in the kitchen, pantry, or dining room. Furthermore, these circuits
- are in addition to any required for refrigerators, stoves, microwaves,
- lighting, etc. Non-dedicated outlets within 6' of a sink *must* be
- protected by a GFCI (NEC only).
-
- Split duplex receptacles are fed with a 220V circuit. The tab
- is broken on the hot side of the outlet, and one hot goes to
- the upper outlet, and the other hot goes to the lower outlet.
- The neutral connects to both outlets through one screw. When
- "carrying through" to another outlet, the neutral must be
- pigtailed, such that removing the outlet, or having the neutral
- connection fall off doesn't cause the neutral to disconnect
- from downstream outlets.
-
- Subject: Where must outlets and switches be in bathrooms?
-
- There must be at least one outlet in each bathroom, adjacent to
- the sink, in addition to any outlet that may be incorporated in
- the light fixture. All such outlets *must* be GFCI-protected.
-
- Subject: What is Romex/NM/NMD? What is BX? When should I use each?
-
- Romex is a brand name for a type of plastic insulated wire.
- Sometimes called non-metallic sheath. The formal name is NM.
- This is suitable for use in dry, protected areas (ie: inside
- stud walls, on the sides of joists etc.), that are not subject
- to mechanical damage or excessive heat. Most newer homes are
- wired almost exclusively with NM wire. There are several
- different categories of NM cable.
-
- BX cable -- technically known as armored cable or "AC" has a
- flexible aluminum or steel sheath over the conductors and is
- fairly resistant to damage.
-
- TECK cable is AC with an additional external thermoplastic
- sheath.
-
- Protection for cable in concealed locations: where NM or AC cable
- is run through studs, joists or similar wooden members, the outer
- surface of the cable must be kept at least 32mm/1.25" (CEC & NEC)
- from the edges of the wooden members, or the cable should be protected
- from mechanical injury. This latter protection can take the form of
- metal plates (such as spare outlet box ends) or conduit.
-
- [Note: inspector-permitted practise in Canada suggests that armored
- cable, or flexible conduit can be used as the mechanical protection,
- but this is technically illegal.]
-
- Additional protection recommendations (these are rules in the
- Canadian codes - they are reasonable answers to the vague
- references to "exposed to mechanical damage" in both the NEC
- and CEC):
-
- - NM cable should be protected against mechanical damage
- where it passes through floors or on the surface of walls
- in exposed locations under 5 feet from the floor.
- Ie: use AC instead, flexible conduit, wooden guards etc.
- - Where cable is suspended, as in, connections to furnaces
- or water heaters, the wire should be protected. Canadian
- practise is usually to install a junction or outlet
- box on the wall, and use a short length of AC cable
- or NM cable in flexible conduit to "jump" to the appliance.
- Stapling NM to a piece of lumber is also sometimes used.
- - Where NM cable is run in close proximity to heating
- ducts or pipe, heat transfer should be minimized by
- means of a 25mm/1" air space, or suitable insulation
- material (a wad of fiberglass).
- - NM cable shall be supported within 300mm/1' of every box
- or fitting, and at intervals of no more than 1.5m/5'.
- Holes in joists or studs are considered "supports".
- Some slack in the cable should be provided adjacent to
- each box. [while fishing cable is technically in violation,
- it is permitted where "proper" support is impractical]
- - 2 conductor NM cable should never be stapled on edge.
- [Knight also insists on only one cable per staple, referring
- to the "workmanship" clause, but this seems more honoured
- in the breach...]
- - cable should never be buried in plaster, cement or
- similar finish.
- - cable should be protected where it runs behind baseboards.
- - Cable may not be run on the upper edge of ceiling joists
- or the lower edges of rafters where the headroom is more
- than 1m (39").
-
- Whenever BX cable is terminated at a box with a clamp, small
- plastic bushings must be inserted in the end of the cable to
- prevent the clamps forcing the sharp ends of the armor through
- the insulation.
-
- BX is sometimes a good idea in a work shop unless covered by
- solid wall coverings.
-
- In places where damage is more likely (like on the back wall of
- a garage ;-), you may be required to use conduit, a
- UL- (or CSA-) approved metal pipe. You use various types of
- fittings to join the pipe or provide entrance/exit for the
- wire.
-
- Service entrances frequently use a plastic conduit.
-
- In damp places (eg: buried wiring to outdoor lighting) you will
- need special wire (eg: CEC NMW90, NEC UF). NMW90 looks like
- very heavy-duty NMD90. You will usually need short lengths of
- conduit where the wire enters/exits the ground. [See underground
- wiring section.]
-
- Thermoplastic sheath wire (such as NM, NMW etc.) should not be
- exposed to direct sunlight unless explicitly approved for that
- purpose.
-
- Canada appears to use similar wire designations to the US,
- except that Canadian wire designations usually include the
- temperature rating in Celsius. Eg: "AC90" versus "AC".
- In the US, NM-B is 90 degrees celcius.
-
- NOTE: local codes vary. This is one of the items that changes
- most often. Eg: Chicago codes require conduit *everywhere*.
- There are very different requirements for mobile homes.
- Check your local codes, *especially* if you're doing anything
- that's the slightest out of the ordinary.
-
- Wire selection table (incomplete - the real tables are enormous,
- uncommon wire types or applications omitted)
-
- Condition Type CEC NEC
-
- Exposed/Concealed dry plastic NMD90 NM
- armor AC90 AC
- TECK90
-
- Exposed/Concealed damp plastic NMD90 NMC
- armor ACWU90
- TECK90
-
- Exposed/Concealed wet plastic NMWU90
- armor ACWU90
- TECK90
-
- Exposed to weather plastic NMWU
- TW etc.
- armor TECK90
-
- Direct earth burial/ plastic NMWU* UF
- Service entrance RWU
- TWU
- armor RA90
- TECK90
- ACWU90
- [* NMWU not for service entrance]
-
-
- Subject: Should I use plastic or metal boxes?
-
- The NEC permits use of plastic boxes with non-metallic cable
- only. The reasoning is simple -- with armored cable, the box
- itself provides ground conductor continuity. U.S. plastic
- boxes don't use metal cable clamps.
-
- The CEC is slightly different. The CEC never permits cable
- armor as a grounding conductor. However, you must still
- provide ground continuity for metallic sheath. The CEC also
- requires grounding of any metal cable clamps on plastic boxes.
-
- The advantage of plastic boxes is comparatively minor even for
- non-metallic sheathed cable -- you can avoid making one ground
- connection and they sometimes cost a little less. On the other
- hand, plastic boxes are more vulnerable to impacts. For
- exposed or shop wiring, metal boxes are probably better.
-
- Subject: Junction box positioning?
-
- A junction box is a box used only for connecting wires together.
-
- Junction boxes must be located in such a way that they're accessible
- later. Ie: not buried under plaster. Excessive use of junction
- boxes is often a sign of sloppy installation, and inspectors may
- get nasty.
-
- Subject: Can I install a replacement light fixture?
-
- In general, one can replace fixtures freely, subject to a few
- caveats. First, of course, one should check the amperage
- rating of the circuit. If your heart is set on installing half
- a dozen 500 watt floodlights, you may need to run a new wire
- back to the panel box. But there are some more subtle
- constraints as well. For example, older house
- wiring doesn't have high-temperature insulation. The excess
- heat generated by a ceiling-mounted lamp can and will cause the
- insulation to deteriorate and crack, with obvious bad results.
- Some newer fixtures are specifically marked for high
- temperature wire only. (You may find, in fact, that your
- ceiling wiring already has this problem, in which case
- replacing any devices is a real adventure.)
-
- Other concerns include providing a suitable ground for some
- fluorescent fixtures, and making sure that the ceiling box and
- its mounting are strong enough to support the weight of a heavy
- chandelier or ceiling fan. You may need to install a new box
- specifically listed for this purpose. A 2x4 across the ceiling
- joists makes a good support. Metal brackets are also available
- that can be fished into ceilings thru the junction box hole and
- mounted between the joists.
-
- There are special rules for recessed light fixtures such as
- "pot" lamps or heat lamps. When these are installed in insulated
- ceilings, they can present a very substantial fire hazard.
- The CEC provides for the installation of pot lamps in insulated
- ceilings, provided that the fixture is boxed in a "coffin" (usually
- 8'x16"x12" - made by making a pair of joists 12" high, and covering
- with plywood) that doesn't have any insulation. (Yes, that's 8 *feet*
- long)
-
- NEC rules are somewhat less stringent. They require at least 3"
- clearance between the fixture and any sort of thermal insulation.
- The rules also say that one should not obstruct free air movement,
- which means that a CEC-style ``coffin'' might be worthwhile.
- Presumably, that's up to the local inspector. [The CEC doesn't
- actually mandate the coffin per-se, this seems to be an inspector
- requirement to make absolutely certain that the fixture can't get
- accidentally buried in insulation. Ie: if you have insulation blown
- in later.]
-
- There are now fixtures that contain integral thermal cutouts and
- fairly large cases that can be buried directly in insulation. They are
- usually limited to 75 watt bulbs, and are unfortunately, somewhat
- more expensive than the older types. Before you use them, you should
- ensure that they have explicit UL or CSA approval for such uses.
- Follow the installation instructions carefully; the prescribed location
- for the sensor can vary.
-
- There does not yet appear to be a heat lamp fixture that is approved
- for use in insulation. The "coffin" appears the only legal approach.
-
- Subject: What does it mean when the lights brighten when a motor starts?
-
- This usually means that the neutral wire in the panel is
- loose. Depending on the load balance, one hot wire may end up
- being more than 110V, and the other less than 110V, with
- respect to ground. This is a very hazardous situation - it can
- destroy your electronic equipment, possibly start fires, and in
- some situations electrocute you (ie: some US jurisdictions
- require the stove frame connected to neutral).
-
- If this happens, contact your electrical authority immediately
- and have them come and check out the problem.
-
- Note: a brief (< 1 second) brightening is sometimes normal with
- lighting and motors on the same 220V with neutral circuit. A
- loose main panel neutral will usually show increased brightness
- far longer than one second. In case of doubt, get help.
-
- Subject: What is 3 phase power? Should I use it? Can I get it in my house?
-
- Three phase power has three "hot" wires, 120 degrees out of
- phase with each other. These are usually used for large motors
- because it is more "efficient", provides a bit more starting torque,
- and because the motors are simpler and hence cheaper.
-
- You're most likely to encounter a 3 phase circuit that shows
- 110 volts between any hot and ground, and 208 volts between
- any two hots. The latter shows the difference between a normal
- 220V/110V common neutral circuit, which is 240 volts between the
- two hots. There are 3 phase circuits with different voltages.
-
- Bringing in a 3 phase feed to your house is usually
- ridiculously expensive, or impossible. If the equipment you
- want to run has a standard motor mount, it is *MUCH* cheaper to
- buy a new 110V or 220V motor for it. In some cases it is
- possible to run 3 phase equipment on ordinary power if you have
- a "capacitor start" unit, or use a larger motor as a
- (auto-)generator. These are tricky, but are a good solution if
- the motor is non-standard size, or too expensive or too big to
- replace. The Taunton Press book ``The Small Shop'' has an
- article on how to do this if you must.
-
- Note that you lose any possible electrical efficiency by using
- such a converter. The laws of thermodynamics guarantee that.
-
- Subject: Is it better to run motors at 110 or 220?
-
- Theoretically, it doesn't make any difference. However, there
- is a difference is the amount of power lost in the supply
- wiring. All things being equal, a 220V motor will lose 4 times
- less power in the house wiring than a 110V motor. This also
- means that the startup surge loss will be less, and the motor
- will get to speed quicker. And in some circumstances, the
- smaller power loss will lead to longer motor life.
-
- This is usually irrelevant unless the supply wires are more
- than 50 feet long.
-
- Subject: What is this nonsense about 3HP on 110V 15A circuits?
-
- It is a universal physical law that 1 HP is equal to 746
- watts. Given heating loss, power factor and other inefficiencies,
- it is usually best to consider 1 HP is going to need 1000-1200
- watts. A 110V 15A circuit can only deliver 1850 watts to a motor,
- so it cannot possibly be more than approximately 2 HP. Given rational
- efficiency factors, 1.5HP is more like it.
-
- Some equipment manufacturers (Sears in particular, most router
- manufacturers in general ;-) advertise a HP rating that is far
- in excess of what is possible. They are giving you a "stall
- horsepower" or similar. That means the power is measured when
- the motor is just about to stop turning because of the load.
- What they don't mention is that if you kept it in that
- condition for more than a few seconds hopefully your breaker
- will trip, otherwise the motor will melt -- it's drawing far
- more current than it can continuously.
-
- When comparing motors, compare the continuous horsepower. This
- should be on the motor nameplate. If you can't find that figure,
- check the amperage rating, which is always present.
-
- Subject: How do I convert two prong receptacles to three prong?
-
- Older homes frequently have two-prong receptacles instead
- of the more modern three. These receptacles have no safety
- ground, and the cabling usually has no ground wire. Neither
- the NEC or CEC permits installing new 2 prong receptacles anymore.
-
- There are several different approaches to solving this:
- 1) If the wiring is done through conduit or BX, and the
- conduit is continuous back to the panel, you can connect
- the third prong of a new receptacle to the receptacle
- box. NEC mainly - CEC frowns on this practise.
- 2) If there is a copper cold water pipe going nearby, and
- it's continuous to the main house ground point, you can
- run a conductor to it from the third prong.
- 3) Run a ground conductor back to the main panel.
- 4) Easiest: install a GFCI receptacle. The ground lug
- should not be connected to anything, but the GFCI
- protection itself will serve instead. The GFCI
- will also protect downstream (possibly also two prong
- outlets). If you do this to protect downstream outlets,
- the grounds must not be connected together. Since it
- wouldn't be connected to a real ground, a wiring fault
- could energize the cases of 3 prong devices connected
- to other outlets. Be sure, though, that there aren't
- indirect ground plug connections, such as via the sheath
- on BX cable.
-
- The CEC permits you to replace a two prong receptacle with a three
- prong if you fill the U ground with a non-conducting goop.
- Like caulking compound. This is not permitted in the NEC.
-
- Subject: Are you sure about GFCIs and ungrounded outlets?
- Should the test button work?
-
- We're sure about what the NEC and CEC say. Remember, though,
- that your local codes may vary. As for the TEST button -- there's
- a resistor connecting the LOAD side of the hot wire to the LINE
- side of the neutral wire when you press the TEST button. Current
- through this resistor shows up as an imbalance, and trips the GFCI.
- This is a simple, passive, and reliable test, and doesn't require
- a real ground to work. If your GFCI does not trip when you press
- the TEST button, it is very probably defective or miswired. Again:
- if the test button doesn't work, something's broken, and potentially
- dangerous. The problem should be corrected immediately.
-
- The instructions that come with some GFCIs specify that the ground
- wire must be connected. We do not know why they say this. The
- causes may be as mundane as an old instruction sheet, or with the
- formalities of UL or CSA listing -- perhaps the device was never
- tested without the ground wire being connected. On the other hand,
- UL or CSA approval should only have been granted if the device
- behaves properly in *all* listed applications, including ungrounded
- outlet replacement. (One of us called Leviton; their GFCIs are
- labeled for installation on grounded circuits only. The technician
- was surprised to see that; he agreed that the NEC does not require
- it, and promised to investigate.)
-
- Subject: How should I wire my shop?
-
- As with any other kind of wiring, you need enough power for all
- devices that will be on simultaneously. The code specifies
- that you should stay under 80% of the nominal capacity of the
- circuit. For typical home shop use, this means one circuit for
- the major power tools, and possibly one for a dust collector or
- shop vac. Use at least 12 gauge wire -- many power tools have
- big motors, with a big start-up surge. If you can, use 20 amp
- breakers (NEC), though CEC requires standard 20A receptacles
- which means you'd have to "replug" all your equipment. Lights
- should either be on a circuit of their own -- and not shared
- with circuits in the rest of the house -- or be on at least two
- separate circuits. The idea is that you want to avoid a
- situation where a blade is still spinning at several thousand
- RPM, while you're groping in the dark for the OFF switch.
-
- Do install lots of outlets. It's easier to install them in the
- beginning, when you don't have to cut into an existing cable.
- It's useful if at least two circuits are accessible at each
- point, so you can run a shop vac or a compressor at the same
- time as the tool you really want. But use metal boxes and
- plates, and maybe even metal-sheathed cable; you may have
- objects flying around at high speeds if something goes a bit
- wrong.
-
- Note that some jurisdictions have a "no horizontal wiring"
- rule in workshops or other unfinished areas that are used
- for working. What this means is that all wiring must be
- run along structural members. Ie: stapled to studs.
-
- Other possible shop circuits include heater circuits, 220V
- circuits for some large tools, and air compressor circuits.
- Don't overload circuits, and don't use extension cords if you
- can help it, unless they're rated for high currents. (A coiled
- extension cord is not as safe as a straight length of wire of
- the same gauge. Also, the insulation won't withstand as much
- heat, and heat dissipation is the critical issue.)
-
- If your shop is located at some remove from your main panel,
- you should probably install a subpanel, and derive your shop
- wiring from it. If you have young children, you may want to
- equip this panel with a cut-off switch, and possibly a lock.
- If you want to install individual switches to ``safe''
- particular circuits, make sure you get ones rated high enough.
- For example, ordinary light switches are not safely able to
- handle the start-up surge generated by a table saw. Buy
- ``horsepower-rated'' switches instead.
-
- Finally, note that most home shops are in garages or unfinished
- basements; hence the NEC requirements for GFCIs apply. And
- even if you ``know'' that you'd never use one of your shop
- outlets to run a lawn mower, the next owner of your house might
- have a different idea.
-
- Note: Fine Woodworking magazine often carries articles on shop
- wiring. April 1992 is one place to start.
-
- Subject: Underground Wiring
-
- You will need to prepare a trench to specifications, use
- special wire, protect the wire with conduit or special plastic
- tubing and possibly lumber (don't use creosoted lumber, it rots
- thermoplastic insulation and acts as a catalyst in the corrosion
- of lead). The transition from in-house to underground wire is
- generally via conduit. All outdoor boxes must be specifically
- listed for the purpose, and contain the appropriate gaskets,
- fittings, etc. If the location of the box is subject to immersion
- in water, a more serious style of water-proof box is needed. And
- of course, don't forget the GFCIs.
-
- The required depths and other details vary from jurisdiction to
- jurisdiction, so we suggest you consult your inspector about
- your specific situation.
-
- A hint: buy a roll of bright yellow tape that says "buried power
- line" and bury it a few inches above where the wire has been placed.
-
- Subject: Aluminum wiring
-
- During the 1970's, aluminum (instead of copper) wiring became
- quite popular and was extensively used. Since that time,
- aluminum wiring has been implicated in a number of house fires,
- and most jurisdictions no longer permit it in new installations.
- We recommend, even if you're allowed to, that do not use it for new
- wiring.
-
- But don't panic if your house has aluminum wiring. Aluminum
- wiring, when properly installed, can be just as safe as copper.
- Aluminum wiring is, however, very unforgiving of improper
- installation. We will cover a bit of the theory behind potential
- problems, and what you can do to make your wiring safe.
-